The Feeder That Delivered 228 V Instead of 240 V
A feeder calculation can miss half the resistance when it counts only the outgoing conductor and forgets the return path.
A feeder calculation can miss half the resistance when it counts only the outgoing conductor and forgets the return path.
A kW-only three-phase current calculation can look correct and still undersize a feeder when power factor is below unity.